Multi-Split Air Conditioner Outdoor Units for Flexible Installation!

  • Independent electronic expansion valve for each indoor unit
  • A wide range of combinations with every type of indoor unit for ultimate flexibility and the ideal atmosphere in every part of your building
  • Ideal choice for island and coastal areas thanks to the unit’s Golden Fin coating
  • A+++* energy class in heating (Warmer Zone) with SCOP 5.1
  • Wide operating range for stable performance

Contact us

Eurovent"

The upgraded range of outdoor Multi-Split Units ensures absolute flexibility for the installation of up to 5 indoor units of each type. Maximum length of cooling pipes up to 75m.

The updated design of the outdoor units contributes to stable operation, easy maintenance and efficient heating, even in low outdoor temperatures. The downward positioning of the electronic parts helps to protect them from dust and to the reliable operation of the unit.

Enjoy excellent temperature conditions and tranquil atmosphere. The advanced design of the unit, featuring larger gaps between air ducts and an improved fan tilt, facilitates airflow and ensures quiet, efficient performance. Additionally, Silent Mode further reduces noise levels, allowing you to enjoy a perfect atmosphere undisturbed.

With the special design of the air conditioner, efficient heating is achieved even when extremely low temperatures prevail. Enjoy an ideal atmosphere even at -15°C.

The air conditioner's sophisticated control design provides effective and efficient cooling operation in areas where special conditions are required, even at -15°C.

In the event of a power failure, the air conditioning unit will automatically restart according to the previous settings.

In the event of unusual behavior, the unit will automatically shut down to protect the system. After a while, a protection code will appear on the screen for immediate repair.

The fans of the indoor and outdoor unit, as well as the compressor, feature DC Inverter technology, allowing for smooth and efficient adjustment of the air conditioner's operation to suit the needs of the space.

  • U6RSL(2)-18
  • Cooling Capacity 18.000 (7.600-19.000) Btu / h
  • Cooling Capacity 5.28 (2.23-5.57) kWatt
  • Heating Capacity 19.000 (7.980-19.200) Btu / h
  • Heating Capacity 5.57 (2.34-5.63) kWatt
  • Seasonal Efficiency
    (in accordance to EN14825)
  • Cooling
  • Pdesign 5.3 kW
  • Energy Class A++
  • SEER 6.1
  • Heating Middle Zone
  • Pdesign 4.3 kW
  • Energy Class A+
  • SCOP 4.0
  • Heating Warm Zone
  • Pdesign 5.0 kW
  • Energy Class A+++
  • SCOP 5.1
  • Voltage/ Frequency/ Phase 220-240/50/1 V / Hz / Ph
  • Indoor Number of Units (Min. - Max.) 1 - 2
  • Noise Level 56 db(A)
  • Sound Power Level 65 db(A)
  • Dimensions
    (WxDxH)
    805x330x554 mm
  • Net Weight 35.0 kg
  • Compressor Type ROTARY
  • Liquid Line/ Gas Line 2 x (1/4” | 3/8”)
  • Fuses 1x16 Α
  • Refrigerant / Charge R32/1.250 g
  • Maximum Pipe Length Total 40 m
  • Maximum Pipe Length
    For One Indoor Unit
    25 m
  • Max. Height Difference
    Between Indoor and Outdoor Unit
    15 m
  • Max. Height Difference
    Between Indoor Units
    10 m
  • Operation Temperature Range
    in Cooling
    -15~50 °C
  • Operation Temperature Range
    in Heating
    -15~24 °C
  • U6RSL(3)-27
  • Cooling Capacity 27.000 (10.200-29.000) Btu / h
  • Cooling Capacity 7.91 (2.99-8.50) kWatt
  • Heating Capacity 28.000 (7.500-29.000) Btu / h
  • Heating Capacity 8.20 (2.21-8.50) kWatt
  • Seasonal Efficiency
    (in accordance to EN14825)
  • Cooling
  • Pdesign 7.9 kW
  • Energy Class A++
  • SEER 6.1
  • Heating Middle Zone
  • Pdesign 5.3 kW
  • Energy Class A+
  • SCOP 4.0
  • Heating Warm Zone
  • Pdesign 5.8 kW
  • Energy Class A+++
  • SCOP 5.1
  • Voltage/ Frequency/ Phase 220-240/50/1 V / Hz / Ph
  • Indoor Number of Units (Min. - Max.) 1 - 3
  • Noise Level 58 db(A)
  • Sound Power Level 68 db(A)
  • Dimensions
    (WxDxH)
    890x342x673 mm
  • Net Weight 48.0 kg
  • Compressor Type ROTARY
  • Liquid Line/ Gas Line 3 x (1/4” | 3/8”)
  • Fuses 1x20 Α
  • Refrigerant / Charge R32/1.850 g
  • Maximum Pipe Length Total 60 m
  • Maximum Pipe Length
    For One Indoor Unit
    30 m
  • Max. Height Difference
    Between Indoor and Outdoor Unit
    15 m
  • Max. Height Difference
    Between Indoor Units
    10 m
  • Operation Temperature Range
    in Cooling
    -15~50 °C
  • Operation Temperature Range
    in Heating
    -15~24 °C
  • U5MRSL32(4)-36
  • Cooling Capacity 36.000 (7.000-36.000) Btu / h
  • Cooling Capacity 10.55 (2.05-10.55) kWatt
  • Heating Capacity 36.000 (8.000-38.000) Btu / h
  • Heating Capacity 10.55 (2.34-11.13) kWatt
  • Seasonal Efficiency
    (in accordance to EN14825)
  • Cooling
  • Pdesign 10.6 kW
  • Energy Class A++
  • SEER 6.1
  • Heating Middle Zone
  • Pdesign 8.4 kW
  • Energy Class A+
  • SCOP 4.0
  • Heating Warm Zone
  • Pdesign 8.8 kW
  • Energy Class A+++
  • SCOP 5.1
  • Voltage/ Frequency/ Phase 220-240/50/1 V / Hz / Ph
  • Indoor Number of Units (Min. - Max.) 1 - 4
  • Noise Level 63 db(A)
  • Sound Power Level 68 db(A)
  • Dimensions
    (WxDxH)
    946x410x810 mm
  • Net Weight 68.8 kg
  • Compressor Type ROTARY
  • Liquid Line/ Gas Line 3 x (1/4” | 3/8”) + 1x (1/4” | 1/2”)
  • Fuses 1x25 Α
  • Refrigerant / Charge R32/2.100 g
  • Maximum Pipe Length Total 80 m
  • Maximum Pipe Length
    For One Indoor Unit
    35 m
  • Max. Height Difference
    Between Indoor and Outdoor Unit
    15 m
  • Max. Height Difference
    Between Indoor Units
    10 m
  • Operation Temperature Range
    in Cooling
    -15~50 °C
  • Operation Temperature Range
    in Heating
    -15~24 °C
  • U6RSL(5)-42
  • Cooling Capacity 42.000 (10.800-42.000) Btu / h
  • Cooling Capacity 12.31 (3.16-12.31) kWatt
  • Heating Capacity 42.000 (11.500-42.000) Btu / h
  • Heating Capacity 12.31 (3.37-12.31) kWatt
  • Seasonal Efficiency
    (in accordance to EN14825)
  • Cooling
  • Pdesign 12.3 kW
  • Energy Class A+
  • SEER 5.8
  • Heating Middle Zone
  • Pdesign 9.5 kW
  • Energy Class A+
  • SCOP 3.8
  • Heating Warm Zone
  • Pdesign 10.1 kW
  • Energy Class A+++
  • SCOP 5.1
  • Voltage/ Frequency/ Phase 220-240/50/1 V / Hz / Ph
  • Indoor Number of Units (Min. - Max.) 1 - 5
  • Noise Level 62 db(A)
  • Sound Power Level 70 db(A)
  • Dimensions
    (WxDxH)
    946x410x810 mm
  • Net Weight 74.1 kg
  • Compressor Type ROTARY
  • Liquid Line/ Gas Line 4x (1/4” | 3/8”) + 1x (1/4” | 1/2”)
  • Fuses 1x25 Α
  • Refrigerant / Charge R32/2.900 g
  • Maximum Pipe Length Total 80 m
  • Maximum Pipe Length
    For One Indoor Unit
    35 m
  • Max. Height Difference
    Between Indoor and Outdoor Unit
    15 m
  • Max. Height Difference
    Between Indoor Units
    10 m
  • Operation Temperature Range
    in Cooling
    -15~50 °C
  • Operation Temperature Range
    in Heating
    -15~24 °C

Useful files of outdoor U6 multi split units

Energy Labels, User - Installation Manuals - Wireless Remote Control - Wi-Fi, Product Fiche, CE Declaration, High Resolution Photos, Technical Specifications & Features

Find more

All you need to know about

Register now using your e-mail and get all the latest news in the world of air conditioning and more …

Thank you for your registration!