Life Pro air conditioners for high energy efficiency and ideal conditions!

  • Wi-Fi Standard for absolute control wherever you are
  • Engineering mode for up to 70% energy saving
  • Excellent performance and energy saving with A+++ Energy Class
  • Ionizer for a healthy environment
  • Follow me for perfect temperature and comfort

Become an Inventor Partner

Removes even the smallest amount of dust from the air. It eliminates germs while reduces the chance of allergies and diseases, providing healthy pure air.

Sterilization HEPA Filter

Triple Action Filter with Vitamin C, Silver Ion and Cold Catalyst protects your skin and improves the air.

Triple Action Filter

Prevent potential weather damages in places that are not heated and pose risks during the winter. Enable the 8°C function and the air conditioner only heats the room as needed while maintaining a stable room temperature of 8°C.

8°C Heating

The ultimate protection of the air conditioner, especially at areas with high humidity levels and increased corrosive possibility, such as islands and coastal areas, can now be achieved. The golden, anticorrosive coating of the outdoor unit’s refrigerant, protects against salty air, rain and other corrosive elements, ensuring the effective performance of the air conditioner and the extension of its lifeline. The golden coating of the indoor unit refrigerant, thanks to its antibacterial action, allows you to enjoy a perfectly clean and healthy atmosphere!

The outdoor unit’s special design produces an efficient and effective heating operation even at -20°C.

It eliminates unwanted moisture in the indoor unit during cooling mode operation. After turning off the air conditioner, the indoor unit’s fan will keep running for a while in order to dry the indoor unit.

Powerful Self-Cleaning

Activate the Ultra Silence Mode and enjoy an absolute feeling of pure silence in your room.

Distributes cool/warm air to maximum area by moving horizontal flaps automatically.

Centralized (for up to 64 indoor units), front desk, touch pad wired controller, wifi and many others.

Set the unit to start and stop automatically in a 24h period.

  • L6VI32-09WF/L6VO32-09
  • Cooling Capacity 9.000 (3.100 - 11.600) Btu / h
  • Cooling Capacity 2.64 (0.91-3.40) kWatt
  • Heating Capacity 10.000 (2.800 - 11.500) Btu / h
  • Heating Capacity 2.93 (0.82-3.37) kWatt
  • Seasonal Efficiency
    (In accordance to ΕΝ14.825)
  • Cooling
  • Pdesign 2.8 kW
  • Energy Class A++
  • SEER 6.3
  • Energy Consumption 156 kWh / year
  • Heating Middle Zone
  • Pdesign 2.6 kW
  • Energy Class A+
  • SCOP 4.0
  • Energy Consumption 910 kWh / year
  • Heating Warm Zone
  • Pdesign 2.6 kW
  • Energy Class A+++
  • SCOP 5.1
  • Energy Consumption 714 kWh / year
  • Voltage / Frequency / Phase 220-240/50/1 V / Hz / Ph
  • Current Input Cooling 3.2 (0.4-5.4) Α
  • Current Input Heating 3.2 (0.5-5.2) Α
  • Power Input Cooling 732 (100-1.240) W
  • Power Input Heating 733 (120-1.200) W
  • Air Flow Volume
    (High/Medium/Low)
    466/360/325 m³ / h
  • Noise Level Indoor Unit (Silent / Low / Med / Hi) 21/25/32/38.5 db(A)
  • Sound Power Level Outdoor Unit 55.5 db(A)
  • Sound Power Level Indoor Unit 54 db(A)
  • Sound Power Level Outdoor Unit 62 db(A)
  • Compressor Type ROTARY
  • Liquid Line / Gas Line 1 / 4” / 3 / 8”
  • Power Supply Wire Outdoor 3 x 1.5 / 10 No x mm² / A
  • Signal Wires 5 × 1.5 No x mm²
  • Dimensions
    Indoor Unit
    (WxDxH)
    805x194x285 mm
  • Dimensions
    Outdoor Unit
    (WxDxH)
    720x270x495 mm
  • Net Weight Indoor / Outdoor 7.6/23.2 kg
  • Refrigerant / Charge R32/0.55 g
  • Operation Temperature Range Outdoor Unit Cooling -15~50 °C
  • Operation Temperature Range Outdoor Unit Heating −20~30 °C
  • L6VI32-12WF/L6VO32-12
  • Cooling Capacity 12.000 (3.800 - 14.200) Btu / h
  • Cooling Capacity 3.52 (1.11-4.16) kWatt
  • Heating Capacity 13.000 (3.700 - 14.400) Btu / h
  • Heating Capacity 3.81 (1.08-4.22) kWatt
  • Seasonal Efficiency
    (In accordance to ΕΝ14.825)
  • Cooling
  • Pdesign 3.6 kW
  • Energy Class A++
  • SEER 6.1
  • Energy Consumption 211 kWh / year
  • Heating Middle Zone
  • Pdesign 2.7 kW
  • Energy Class A+
  • SCOP 4.0
  • Energy Consumption 945 kWh / year
  • Heating Warm Zone
  • Pdesign 2.5 kW
  • Energy Class A+++
  • SCOP 5.1
  • Energy Consumption 686 kWh / year
  • Voltage / Frequency / Phase 220-240/50/1 V / Hz / Ph
  • Current Input Cooling 5.38 (0.5-6.9) Α
  • Current Input Heating 4.42 (0.4-6.9) Α
  • Power Input Cooling 1.213 (130-1.580) W
  • Power Input Heating 1.088 (100-1.680) W
  • Air Flow Volume
    (High/Medium/Low)
    540/430/314 m³ / h
  • Noise Level Indoor Unit (Silent / Low / Med / Hi) 21/25/34.5/40.5 db(A)
  • Sound Power Level Outdoor Unit 56 db(A)
  • Sound Power Level Indoor Unit 55 db(A)
  • Sound Power Level Outdoor Unit 63 db(A)
  • Compressor Type ROTARY
  • Liquid Line / Gas Line 1 / 4” / 3 / 8”
  • Power Supply Wire Outdoor 3 x 1.5 / 10 No x mm² / A
  • Signal Wires 5 × 1.5 No x mm²
  • Dimensions
    Indoor Unit
    (WxDxH)
    805x194x285 mm
  • Dimensions
    Outdoor Unit
    (WxDxH)
    720x270x495 mm
  • Net Weight Indoor / Outdoor 7.6/23.2 kg
  • Refrigerant / Charge R32/0.55 g
  • Operation Temperature Range Outdoor Unit Cooling -15~50 °C
  • Operation Temperature Range Outdoor Unit Heating −20~30 °C
  • L6VI32-18WF/L6VO32-18
  • Cooling Capacity 18.000 (6.200 - 21.000) Btu / h
  • Cooling Capacity 5.28 (1.82-6.15) kWatt
  • Heating Capacity 19.000 (4.400 - 23.000) Btu / h
  • Heating Capacity 5.57 (1.29-6.74) kWatt
  • Seasonal Efficiency
    (In accordance to ΕΝ14.825)
  • Cooling
  • Pdesign 5.2 kW
  • Energy Class A++
  • SEER 7.4
  • Energy Consumption 247 kWh / year
  • Heating Middle Zone
  • Pdesign 4.1 kW
  • Energy Class A+
  • SCOP 4.0
  • Energy Consumption 1.435 kWh / year
  • Heating Warm Zone
  • Pdesign 4.4 kW
  • Energy Class A+++
  • SCOP 5.1
  • Energy Consumption 1.208 kWh / year
  • Voltage / Frequency / Phase 220-240/50/1 V / Hz / Ph
  • Current Input Cooling 6.7 (0.6-10.0) Α
  • Current Input Heating 6.8 (0.9-10.2) Α
  • Power Input Cooling 1.550 (140-2.300) W
  • Power Input Heating 1.570 (220-2.350) W
  • Air Flow Volume
    (High/Medium/Low)
    840/680/540 m³ / h
  • Noise Level Indoor Unit (Silent / Low / Med / Hi) 20/26/36/42.5 db(A)
  • Sound Power Level Outdoor Unit 56 db(A)
  • Sound Power Level Indoor Unit 56 db(A)
  • Sound Power Level Outdoor Unit 63 db(A)
  • Compressor Type ROTARY
  • Liquid Line / Gas Line 1 / 4” / 1 / 2”
  • Power Supply Wire Outdoor 3 × 2.5 / 16 No x mm² / A
  • Signal Wires 5 × 1.5 No x mm²
  • Dimensions
    Indoor Unit
    (WxDxH)
    957x213x302 mm
  • Dimensions
    Outdoor Unit
    (WxDxH)
    805x330x554 mm
  • Net Weight Indoor / Outdoor 10.0/32.7 kg
  • Refrigerant / Charge R32/1.08 g
  • Operation Temperature Range Outdoor Unit Cooling -15~50 °C
  • Operation Temperature Range Outdoor Unit Heating −20~30 °C
  • L6VI32-24WF/L6VO32-24
  • Cooling Capacity 24.000 (7.100 - 27.000) Btu / h
  • Cooling Capacity 7.03 (2.08-7.91) kWatt
  • Heating Capacity 25.000 (5.500 - 27.000) Btu / h
  • Heating Capacity 7.33 (1.61-7.91) kWatt
  • Seasonal Efficiency
    (In accordance to ΕΝ14.825)
  • Cooling
  • Pdesign 7.0 kW
  • Energy Class A++
  • SEER 6.1
  • Energy Consumption 405 kWh / year
  • Heating Middle Zone
  • Pdesign 4.8 kW
  • Energy Class A+
  • SCOP 4.0
  • Energy Consumption 1.680 kWh / year
  • Heating Warm Zone
  • Pdesign 5.6 kW
  • Energy Class A+++
  • SCOP 5.1
  • Energy Consumption 1.537 kWh / year
  • Voltage / Frequency / Phase 220-240/50/1 V / Hz / Ph
  • Current Input Cooling 11.5 (1.8-13.8) Α
  • Current Input Heating 11.0 (1.3-12.2) Α
  • Power Input Cooling 2.600 (420-3.150) W
  • Power Input Heating 2.400 (300-2.750) W
  • Air Flow Volume
    (High/Medium/Low)
    980/817/662 m³ / h
  • Noise Level Indoor Unit (Silent / Low / Med / Hi) 30/36/40.5/45 db(A)
  • Sound Power Level Outdoor Unit 59 db(A)
  • Sound Power Level Indoor Unit 59 db(A)
  • Sound Power Level Outdoor Unit 67 db(A)
  • Compressor Type ROTARY
  • Liquid Line / Gas Line 3 / 8” / 5 / 8”
  • Power Supply Wire Outdoor 3 × 2.5 / 16 No x mm² / A
  • Signal Wires 5 × 1.5 No x mm²
  • Dimensions
    Indoor Unit
    (WxDxH)
    1040x220x327 mm
  • Dimensions
    Outdoor Unit
    (WxDxH)
    890x342x673 mm
  • Net Weight Indoor / Outdoor 12.3/42.9 kg
  • Refrigerant / Charge R32/1.42 g
  • Operation Temperature Range Outdoor Unit Cooling -15~50 °C
  • Operation Temperature Range Outdoor Unit Heating −20~30 °C

With the Sleep Mode, the air conditioner adjusts the room temperature for perfect sleeping conditions and great energy savings.

This function gives you a boost in cooling and heating power for a period and makes the room cool down or heat up rapidly.

Want to turn off the AC beep and display? By pressing the mute operation, Inventor AC helps to give you a quiet and comfortable night.

The outdoor unit’s special design produces an efficient and effective cooling operation even at -15°C.

The perceived temperature by the indoor unit sensor may vary from the real temperature of the room, due to the position of the unit. Thanks to this function you can minimize the difference and achieve better conditions in your place.

The indoor coil sensor controls the indoor fan and prevents cold air from entering the room during start up in heating mode.

Horizontal louver will automatically move to the same position as you set last time when the unit turned on.

If the air conditioner breaks off unexpectedly due to the power cut, it will restart with the previous setting mode automatically when the power resume.

Up to 12 grades indoor fan speeds, ensure more accurate control and brings more comfortable air flow.

Due to the DC fan motor, outdoor fan speeds increase from 2 grades to 5 grades, more comfortable and reinforces energy saving.

Both left and right sides of the indoor unit are possible for drainage hose connection, easy for installation.

When temperature sensor error happens, the air conditioner will display error code and stop immediately, while AC displays error and continues running in a proper status, to avoid the case that AC is in urgent need.

Indoor unit will show error code “EC” and will stop automatically when refrigerant leakage is detected.

Once abnormal operation or parts failure happens, the unit will shut off automatically to protect the system. Meanwhile it will indicate protection or error code for fast service.

The R32 ECO Refrigerant with 68% lower global warming potential, is here to significantly enhance your air conditioner performance and to drastically contribute to global warming protection. It does not adversely affect the ozone layer, contributes in reducing global warming effect by entrapping smaller amounts of heat (GWP = 675) and can be easily reused and recycled.

The fan motors of the indoor and outdoor units as well as the compressor have been upgraded to All DC Inverter technology. In this way, the compressor can change the capacity depending on the needs of the indoor atmosphere and create perfect conditions in your space.

Media Library Life Pro (LV6)

User, Remote Controller, Wi-Fi & Installation Manuals - Energy Labels - High Resolution Photos - CE Declaration - Technical Specifications

Find more

All you need to know about

Register now using your e-mail and get all the latest news in the world of air conditioning and more …